Test Specification TC15.01

Validation of Coordinated Voltage Control algorithm based on combined CHIL and PHIL test

Test Specification Definition

ID

TC15.01

Reference to Test Case

15

Title of Test

Validation of Coordinated Voltage Control algorithm based on combined CHIL and PHIL test

Test Rationale

To validate the successful operation of the system when using hierarchical control and the effective implementation of the communication scheme when using hardware MicroGrid Central Controller in real conditions

Specific Test System (graphical)

Target measures
  • Active and reactive power of loads
  • Active and reactive power of PVs and BESS
  • SoC of BESS
  • Tap position of the OLTC
  • Bus voltages
Input and output parameters

Input to CVC:

  • Active and reactive power of loads
  • Active power of PVs
  • SoC of BESS
  • Tap position of the OLTC

Output of the CVC:

  • Active and reactive power of the BESS
  • Reactive power of the PV Inverters
  • Tap position of the OLTC
Test Design
  1. Initialization of the voltage control algorithm
  2. Reception of input parameters from the network via the MGCC
  3. Solution of the optimization problem
  4. Dispatch of optimal set points to the voltage regulating devices via the MGCC
  5. Save the simulation results for each iteration
  6. Repeat steps 2 to 5 in pre-configured intervals
Initial system state
  • Power system in steady-state
  • Controller up and running
  • Communications established
  • OLTC Controller up and running
  • DER Storage Controller up and running
  • DERGen Controller up and running
  • Optimal power flow solution achieved
Evolution of system state and test signals

Mitigation of voltage deviations

Other parameters

N/A

Temporal resolution

N/A

Source of uncertainty

Convergence of the optimization algorithm, communication Interfaces and delays

Suspension criteria / Stopping criteria

Communication failures, abnormal system conditions