Test Specification TC11.TS02
Test Specification Definition
ID | TC11.TS02 |
---|---|
Reference to Test Case | TC11 |
Title of Test | Local controller responds to service requests from aggregator controller |
Test Rationale | This test characterizes district operation with and without Booster Heater Controller and Electric Storage Controller active, seeking to demonstrate that the local controllers respond to service requests from the aggregator controller. |
Specific Test System (graphical) | The system under test includes an electrical system, a district heating system and a control system. Each is sketched below. Thermal system The block called “Row Houses” consists of multiple small loads which are aggregated into a single, larger load. Electrical system Note, that only loads which are marked in red are inside the quarter under control. All buses are taken to be P-Q buses, with the grid acting as the slack bus. Rings 3-5 are summarized, as no buses are inside the district. Control domain coupling The distribution grid management does not form part of the system under test, but are taken as exogenous signals. |
Target measures | See Test Design. |
Input and output parameters |
|
Test Design | The test comprises 24 hours of district operation. During these 24 hours, the heat pump controller is asked to keep the forward temperature of the connected pipe above 70ºC. Further, these services are requested of the Aggregator by the Distribution Grid Management:
where these limits are defined as below. The test consists of several runs:
By comparing these runs, whether the controllers respond to service requests can be established. For run 1, set:
For subsequent runs (given the 99% quantile of district electrical import P_i_99 and the 1% quantile of district electrical import, P_i_1), the system is asked to restrict its import relative to the uncontrolled base case:
|
Initial system state |
|
Evolution of system state and test signals | Test signals:
|
Other parameters | N/A |
Temporal resolution | The test is run at a fixed time step of 10 seconds. |
Source of uncertainty | Since the exact electrical demand signal consists of a deterministic trend and a randomized factor, each “run” above should be repeated 10 times, with the mean and standard deviation of each target metric recorded. |
Suspension criteria / Stopping criteria | N/A |