The validation of the FFR and SI control allows to evaluate the ability of the converter to provide these functions, considering also the variability attributes (Frequency variation, power set-point, voltage and current harmonics, measures accuracy).
This TS requires a grid simulator and one power converter with the OuI.
Power and frequency measures time series of the power converter under test.
Frequency set-point, FCR, FFR and SI control mode ON/OFF, Power baseline.
A simulation and/or a pure hardware experiment can be performed. A Pure hardware experiment is recommended but, with some assumption, also a simpler experiment can be performed.
The test design for verifying the PoI 1 is the following:
Frequency: 50 Hz Power baseline: at least three different initial states; one with lower power exchange, one with medium power exchange and one with high power exchange.
From 50 Hz up to 51.5 Hz, then down to 47.5 Hz with different step size (0.1 Hz, 0.25, 0.5 Hz).
See variability attributes.
At least 0.1 ms.
Measures accuracy in case of non-simulation experiments.
Disconnection of the power converter.